 SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
Features * Ideal server form factor optimizes, space,
efficiency, and load variations
* High efficiency maximized between 30-80% load conditions * Unconditionally stable under any load condition * NEBS level 3 compliance (GR-63, -78, -1089) * Wide range DC-input model available (SFD550-12BG) * Wide input voltage range (90-264 VAC)
with PFC 1U or 2U height configurations Active current share with ORing FET I2C interface status and control Standby voltage of 3.3 VDC @ 3 A Overtemperature, overload, and overvoltage protection * Status LEDs: AC OK, DC OK, and Overtemperature
Applications * Datacom * Distributed power systems
* * * * *
Description The SFP650-12BG is a 650-watt, power factor corrected (PFC) front-end which provides a 12 VDC output for datacom and other distributed power applications. Its compact size enables mounting in both 1U and 2U height racks. High efficiencies, advanced thermal management techniques, and an internal fan increase reliability over a broad range of operating conditions. Internal ORing diodes facilitate use in hot-swap, redundant configurations. Status is provided with front panel LEDs, logic signals, and via the I2C management interface bus. In addition, the I2C bus can enable the power supply and control fan speed. The SFP650-12BG meets international safety requirements and is CE marked to the Low Voltage Directive (LVD).
Model Selection
Model Nominal Output Voltage (VDC) 12 3.3 (Standby) Adjustment Range (VDC) Maximum Output Current (Amps) 53.3 3 Regulation % 3 3 Ripple & Noise @ 20 MHz BW (mV) 100 100
SFP650-12BG
N/A N/A
FEB 21, 2007
Page 1 of 9
www.power-one.com
SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
Input Specifications
Parameter AC Input Voltage Input Frequency Hold-up Time Input Current Inrush Surge Current Power Factor Conditions/Description Single-phase continuous input range. AC input. After last AC line peak at full power. At 115 VAC. At full-rated load. At 90 VAC. Min. 90 47 20 6 15 > 0.95 Nom. Max. 264 63 Units VAC Hz ms A rms A pk W/VA
Excluding Xcap. Vin = 264 VAC. 25 C Per EN61000-3-2
Output Specifications
Parameter Efficiency Minimum Load Output Power Overshoot Transient Response Output voltage overshoot at turn-on. Maximum recovery time to within 1% of initial set point due to a 25% load change, 1A/s. 12V output: Standby output: Maximum deviation: Turn-On Delay with PS_ON signal Output Regulation 12V output: Standby output: Conditions/Description Full rated load at 220 VAC input. Minimum loading required to maintain regulation. Min. 89 0 650 <5 Nom. Max. Units % A W %
5 5 3 3 1500
ms ms % % ms
Time required for initial output voltage stabilization after application of AC input or ON/OFF signal. See Model Selection data on page 1.
FEB 21, 2007
Page 2 of 9
www.power-one.com
SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
Interface Signals and Internal Protection1
Parameter Overvoltage Protection Overcurrent Protection Short-Circuit Protection Overtemperature/ Fan Failure Warning Conditions/Description Latch-style overvoltage protection. Current limit (Latching Mode). 12V output: Standby output: Latching Mode. 12V output will shut down in the event of an overtemperature condition or blocked fan rotor. OT setpoint is 62 3 C. Supply's fan and Vaux are active. Power supply will recover when OT condition is removed. Amber OT LED will turn ON to indicate fault condition. Output enable. Pulled low on conjunction with PS_ON being pulled low allows V1 to be activated. 0 to 8V signal used for active current sharing. For factory use only. I2C Address. I2C Data line (3.3V). I2C Clock line (3.3V). Two pulses per fan revolution. High signal indicates AC is within PSU limits. 100 Ohm resistor internally connected to RTN allowing the PSU to be detected on insertion. Low signal indicates PSU fan is running below speed or an overtemperature limit was exceeded. High signal indicates both outputs are within regulation limits. 38.4 3.2 Min. Nom. Max. 15 4.3 47.6 6 Units V A
PS_KILL +12V Current Share Write Protect PS A0 SDA SCL Tach AC_OK/H Present/L Alert/L PWROK/H
1
Refer to product specification for internal pull up impedances and timing of these signals.
FEB 21, 2007
Page 3 of 9
www.power-one.com
SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
I2C Bus Management Interface1
Static Status (Logic 1 or 0) Includes static information such as: part number and revision level, output rating, serial number, date code, and manufacturing location. AC Input OK. DC Output OK. Overtemperature. Overcurrent. Fan OK. Overvoltage Alert Undervoltage Alert Output voltage (main output). LSB = 20 mV Output current (main output). LSB = 50 mA
Real-Time Monitoring
1
Reference "I C Management Interface" and "EEPROM Table of Contents" documents for SFP450-12BG (consult factory).
2
Safety, Regulatory, and EMI Specifications
Parameter Agency Approvals Electromagnetic Interference Harmonics Voltage Fluctuation and Flicker ESD Susceptibility Radiated Susceptibility EFT/Burst Input Transient Protection RF Conducted Disturbances Voltage Interruptions Conditions/Description Min. Nom. Max. Units UL60950, (UL) CSA 60950 (cUL), EN60950 (TUV), CE Mark for LVD. FCC CFR title 47 Part 15 Sub-Part B, EN55022/CISPR 22. Per IEC61000-3-2. Per IEC61000-3-3. Per EN61000-4-2, Level 4. Per EN 61000-4-3, Level 3. Per EN 61000-4-4, Level 4. Per EN 61000-4-5, Class 3. Per EN 61000-4-6, Level 3. Per EN 61000-4-11, performance criterion B 30%. Per EN 61000-4-11, performance criterion C 60%. Per EN 61000-4-11, performance criterion C 95%. Per SEMI F47-0999 > 100 VAC. No output voltage interruption. Per EN60950. At 240 VAC: Line-to-Line: Line-to-Ground: Conducted: Radiated: A A A Pass 8 10 4 1 2 10 10 100 5 . . . . . . kV V/M kV kV V ms ms Sec Class Class
Voltage Sag Immunity Leakage Current
. 1.75 mA
FEB 21, 2007
Page 4 of 9
www.power-one.com
SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
Environmental Specifications
Parameter Altitude Operating Temperature Storage Temperature Temperature Coefficient Relative Humidity Shock 0 C to 45 C (after 15-minute warm-up). Non-condensing. Operating: half-sine, 10 ms, 3-axis. Non-Operating: half-sine, 10 ms, 3-axis. Vibration Operating: swept sine 5-2000-5 Hz, 5-32 Hz, 0.02iDA, 32-2000 Hz. Non-operating: random 10-2000 Hz. Conditions/Description Operating. Non-Operating. Internal DC fan for cooling. At 100% load: 0 -40 Min. Nom. Max. 10K 40K 50 85 0.02 95 +20 +40 1 Units ASL ft ASL ft C C %/C %RH Gpk Gpk Gpk
6.15
Grms
Reliability
Parameter MTBF Conditions/Description (Calculated) MILHDBK 217F Ground Benign. Demonstrated. Useful Life. Min. 100 000 200 000 10 Nom. Max. Units hrs hrs yrs
LED Indicators
Indicatorr Power Good AC OK FAIL LED Color GREEN GREEN (Input > 85 VAC AMBER
FEB 21, 2007
Page 5 of 9
www.power-one.com
SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
Mechanical Drawings
Weight: 1.46 kg (3.22 lb)
FEB 21, 2007
Page 6 of 9
www.power-one.com
SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
Connector Information Power Supply:
Input - IEC 320 input (Male) standard line cord connection Output - P/N FCI 51721-10002406AA or equivalent
Mating Connections:
Input - IEC 320 output (Socket) Standard line cord (15A) Output - P/N: FCI 51741-10002406CC
Input IEC Connector
Input Location
Chassis (Safety) Ground Line 1 (Line) Line 2 (Neutral)
Ground L N
FEB 21, 2007
Page 7 of 9
www.power-one.com
SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
FEB 21, 2007
Page 8 of 9
www.power-one.com
SFP650-12BG AC-DC Front-End Data Sheet 12V Output, 650 Watts
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
FEB 21, 2007
Page 9 of 9
www.power-one.com


▲Up To Search▲   

 
Price & Availability of SFP650-12BG

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X